ESP M1

ESP M1

ESP M1 Series are an combined Type 1, 2 and 3 tested protector (to BS EN 61643) for use on mains power distribution systems primarily to protect connected electronic equipment from transient over voltages on the mains supply, e.g. computer, communications or control equipment. For use at boundaries up to LPZ 0 to protect against flashover (typically the main distribution board location, with multiple metallic services entering) through to LPZ 3 to protect sensitive electronic equipment

Short Circuit Withstand Capability: 25 kA, 50 Hz
Frequency Range: 47-63 Hz
Max. Back-up Fuse: 125 A
Leakage Current (to earth): <250 μA
Indicator Circuit Current: <10 mA
Volt Free Contact² : Screw Terminal / Current rating 1 A / Nominal Voltage (RMS) 250 V
Temperature Range: -40°C to + 80°C
Connection Type: Screw Terminal (Max Torque 2.65Nm)
Conductor Size (stranded): 16mm²
Earth Connection: Screw Terminal (Max Torque 2.65Nm)
Volt Free Contact: Connect via screw terminal with conductor up to 2.5mm² (stranded)
*Protection: *IP20
See Downloads Tab for full Datasheet, Fitting Instructions and DofC

Swipe table
ESP240M1 Single phase, full mode 240 V 280 V 350 V 200-280 V WBX 3 0.6 £434.25 £521.10
ESP415M1 3 Phase, Full Mode 240 V 280 V 350 V 346-484 V WBX 4 1.0 £824.30 £989.16
ESP415M1R 3 Phase, Full Mode with remote display 240 V 280 V 350 V 346-484 V WBX 4 1.1 £928.49 £1,114.19

To help improve our website we use cookies, by using this site you agree that we may store these on your device. For more information on what cookies are and why we use them please read our Cookies and Privacy Policy.